Diesel Generator Fuel Consumption and Cost per kWh

Author

Hisham Abdalla

Date Published

Illustration of a diesel generator set in a canopy beside a raised fuel tank, with a power cable running to a small plant building

Disclaimer: Research and analysis by the engineering team. Fuel figures come from the manufacturer data sheets linked below. The dollar cost inputs are hypothetical. Sources referenced below.

Diesel generator fuel consumption in litres per hour is the electrical output in kW multiplied by the litres burned per kWh at that load. On three Cummins 50 Hz data sheets, covering prime sets from 80 kW to 364 kW, that figure is 0.26 to 0.31 litres per kWh at full load and 0.28 to 0.36 at a quarter of rating. Cost per kWh is that number times the price of a litre, plus maintenance and the cost of owning the set.

Fuel is the largest share, but the part that changes most with how a set is run is the part that never appears on a diesel receipt. This article gives the formula, a grid of manufacturer figures, a worked cost per kWh with every input stated, and a check you can run on your own meter.

The Formula: From Kilowatts to Litres per Hour

Three lines cover the arithmetic.

Litres per hour. Output in kW times litres per kWh at that load. A set delivering 150 kW at 0.2553 litres per kWh burns 150 x 0.2553 = 38.3 litres an hour.

Fuel cost per kWh. Litres per kWh times the price of a litre. If diesel costs $1.20 a litre, which is an input chosen for this example and not a market quote, then 0.2553 x 1.20 = $0.306 per kWh.

Total cost per kWh. Fuel, plus maintenance cost per running hour divided by the average kW, plus the annual cost of owning the set divided by the kWh it delivers in a year.

Manufacturers sometimes quote specific fuel consumption in grams per kWh instead. Converting needs the fuel density. A Cat dealer data sheet for a Perkins-engined 220 kVA set states that its figures assume diesel with a specific gravity of 0.85 (data sheet). At that density, 0.2553 litres is 0.2553 x 0.85 = 0.217 kg, or about 217 g per kWh of electrical output. The density a sheet assumes changes the litres it reports, so check it before comparing one brand's figures with another's.

Three lines of arithmetic from load to cost per kWh: litres per hour equals output in kW times litres per kWh, fuel cost per kWh equals litres per kWh times the diesel price, and total cost adds maintenance and ownership

From electrical load to cost per kWh. The diesel price is a stated input. Source: MIMAH engineering practice; litres per kWh from Cummins C275 D5 data sheet.

Fuel Consumption at 25, 50, 75 and 100 Percent Load

Cummins prints fuel consumption on each 50 Hz data sheet at one quarter, one half, three quarter and full load. Three are used here, all issued in 2017: the C110 D5 (6B), the C275 D5 and the C500 D5. The grid uses their prime ratings of 80, 200 and 364 kW. Each sheet lists the load fractions under its own rating, so the prime columns are read against the prime kW. Litres per kWh is litres per hour divided by the kW at that load, rounded.

At a quarter, half, three quarter and full load, the C110 D5 reads 6.8, 12.0, 18.0 and 24.7 litres an hour, which over 20, 40, 60 and 80 kW gives 0.340, 0.300, 0.300 and 0.309. The C275 D5 reads 14.2, 25.8, 38.3 and 52.5 litres an hour, which over 50, 100, 150 and 200 kW gives 0.284, 0.258, 0.255 and 0.263. The C500 D5 reads 32.9, 51.6, 71.9 and 94.3 litres an hour, which over 91, 182, 273 and 364 kW gives 0.362, 0.284, 0.263 and 0.259.

A grid of fuel consumption at 25, 50, 75 and 100 percent load in litres per hour and litres per kWh for three Cummins prime rated sets of 80, 200 and 364 kW

Fuel consumption of three Cummins 50 Hz prime rated sets at four loads, with litres per kWh calculated from litres per hour. Source: Cummins generator set data sheets for the C110 D5, C275 D5 and C500 D5, 2017.

Three patterns show up.

The best figure sits at half load or above. The C275 D5 burns least per kWh at three quarter load, the C500 D5 at full load, and the C110 D5 is flat from half to three quarter load. None of the three is at its best at a quarter of rating.

The penalty at a quarter load varies by set. The C110 D5 burns 10 percent more per kWh at a quarter load than at full load (0.340 against 0.309), the C275 D5 8 percent more, and the C500 D5 40 percent more (0.362 against 0.259). Do not assume one penalty for every set.

The sheet is the best case. It describes a healthy engine at the maker's test conditions. Injector wear, a clogged air filter, high ambient temperature and altitude all push a real set above its sheet.

Read the right columns. Each sheet prints a standby block and a prime block, and the standby block is for a higher kW. The C500 D5 lists 500 kVA (400 kW) standby against 455 kVA (364 kW) prime, and 103.6 litres an hour at full standby load against 94.3 at full prime load. Standby ratings are for covering a utility failure, not for running the site, so a set that carries a plant for thousands of hours a year should be read and sized on its prime figures. Our diesel generator maintenance schedule explains the ISO 8528-1 rating classes.

Light load costs more per kWh because an engine has to turn itself, its pumps and its fan whatever the electrical load. The C500 D5 sheet lists a radiator fan load of 18.5 kWm, and a fan driven from the engine does not stop taking power when the load falls. At a quarter of prime load that set delivers 91 kW, so the fan alone is about a fifth of the electrical output (18.5 / 91 = 0.20). Every fixed loss is spread across fewer kWh.

Low load also does mechanical harm. The same maintenance schedule covers wet stacking, which begins when a diesel runs below roughly 30 percent load for long periods, and our guide to generator load bank testing covers how to load a set properly.

Worked Example: Cost per kWh at Three Quarter Load and at a Quarter Load

Take the C275 D5 prime set, 200 kW, running 4,000 hours a year. The inputs below are assumptions for the arithmetic. Replace each with your own figure.

Diesel. $1.20 per litre.

Capital. The set bought and installed for $55,000, written off over 8 years at 10 percent. The annual charge is the price times r(1 + r)^n / ((1 + r)^n - 1), which is 0.10 x 2.1436 / 1.1436 = 0.18744. That gives $55,000 x 0.18744 = $10,309 a year.

Maintenance. Oil, filters, labour and an overhaul reserve at $4 per running hour, which is $16,000 a year.

At three quarter load (150 kW). The sheet gives 38.3 litres an hour. Energy is 150 x 4,000 = 600,000 kWh. Fuel is 38.3 x 4,000 = 153,200 litres, which costs 153,200 x 1.20 = $183,840, or $0.3064 per kWh. Maintenance adds 16,000 / 600,000 = $0.0267, capital adds 10,309 / 600,000 = $0.0172, and the total is $0.3064 + $0.0267 + $0.0172 = $0.3503 per kWh. Fuel is 87 percent of it.

At quarter load (50 kW). The sheet gives 14.2 litres an hour. Energy is 50 x 4,000 = 200,000 kWh. Fuel is 14.2 x 4,000 = 56,800 litres, costing $68,160, or $0.3408 per kWh. Maintenance adds 16,000 / 200,000 = $0.0800, capital adds 10,309 / 200,000 = $0.0515, and the total is $0.3408 + $0.0800 + $0.0515 = $0.4723 per kWh. Fuel is 72 percent of it.

The same 200 kW prime set costs 0.3503 dollars per kWh at three quarter load and 0.4723 dollars per kWh at quarter load once fuel, maintenance and capital are added

A hypothetical cost per kWh for one prime set at two load levels. Diesel price, capital and maintenance are stated assumptions. Source: Cummins C275 D5 data sheet; MIMAH engineering practice.

The same engine on the same fuel over the same hours costs 35 percent more per kWh at a quarter load. Fuel per kWh rose by only 11 percent (0.3408 against 0.3064). The rest is maintenance and capital spread over a third of the energy. A set that spends most of its life lightly loaded loses money in two places, which is why sizing it to the load matters as much as the price of diesel.

Real maintenance cost does not stay the same per hour at every load, and a light-load set may need more cleaning and sooner overhauls. Read the example for its shape and put your own dollars in.

Diesel price moves the result more than anything else. Each $0.10 on the price of a litre adds 0.2553 x 0.10 = $0.026 to the cost per kWh at three quarter load, and 0.284 x 0.10 = $0.028 at quarter load. If diesel doubled from $1.20 to $2.40, fuel alone at three quarter load would go from $0.3064 to 0.2553 x 2.40 = $0.6127 per kWh, while maintenance and capital would not change.

What a Litre Costs in Nigeria

The National Bureau of Statistics publishes a monthly Automotive Gas Oil (Diesel) Price Watch. The newest report in its catalogue, dated June 2026, gives a national average retail price of ₦3,277.47 per litre for May 2026. That is 32.44 percent above ₦2,474.69 in April 2026 and 86.40 percent above ₦1,758.26 in May 2025.

At the May 2026 price, fuel alone for the example set costs 0.2553 x 3,277.47 = ₦837 per kWh at three quarter load and 0.284 x 3,277.47 = ₦931 per kWh at quarter load. Add maintenance and capital to get the full figure.

Treat that price as a dated reference. We found no later NBS report when this was written in November 2026, and a series that moved by a third in one month can be well out of date in five. The number that matters is the price on your last delivery note. Our comparison of solar and diesel generation in Nigeria works through a full naira example for a small set, using an older ₦1,700 a litre and about 0.43 litres per kWh for a 30 kVA set, so reprice it before you rely on it.

Costs the Example Leaves Out

Fuel that you pay for and never burn belongs in the total: spillage, evaporation and theft from site tanks. So does the operator's time, the cost of an unplanned stop and the cost of an overhaul that arrives sooner on a hard-worked engine. The example folded overhaul into a maintenance rate. In your own sums, ask the manufacturer or your service provider for the overhaul interval in running hours for your duty, prime or standby, and price it separately.

Checking Your Own Set

You can replace the sheet with measurement in a week.

Litres. Record the fuel used over a period, from a flow meter or from tank dips either side of a known delivery.

Energy. Read the set's kWh meter over the same period. If it has none, use running hours times average kW from the controller.

Divide. Litres over kWh is your figure. Compare it with the sheet value at your average load.

If the measured number is well above the sheet, check the tank and fuel system for losses first, then the injectors and the air filter. A slow rise over months is an early sign of a wearing engine, which is why litres per kWh is worth logging.

What to Do If the Numbers Look Bad

First work out your average load as a fraction of the prime rating. If it sits below about 40 percent for most of the hours, you have three options. A smaller set, or two smaller sets with one running at a time, brings the load fraction up. A 150 kW demand is three quarters of the C275 D5 but only 41 percent of the C500 D5. The grid shows the C275 D5 at 0.255 litres per kWh at that point, while the C500 D5 sits between 0.284 at half load and 0.362 at a quarter. Solar and a battery cut the hours at which the generator runs at all, which our guide to hybrid solar systems explains, and the solar payback calculator gives a first answer on your own diesel spend. Or leave the set as it is and treat the extra cost per kWh as the price of resilience.

MIMAH's maintenance team covers preventive and emergency maintenance and performance diagnostics for rotating equipment, including diesel generating sets. If you want a measured litres-per-kWh figure for a set, or a view on whether it is the right size for its duty, get in touch.